Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03499
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/03/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the sequence of operation for the restroom exhaust fan in the men's restroom so that all of the air supplied to the restroom will be exhausted (i.e. exhaust shall continue even if the lights are off). Reference: Section 403.2.1 (4), IMC 2006. 2. Comment not addressed. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
07/13/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03499 5169 S Santa Cruz TI OLD NAVY The electrical plans have been denied for the following, address each item and indicate how each was addressed. All items per 2005 NEC 1. Provide a fault current analysis, beginning at utility on through to panels.Indicate how fault current levels to be brought to safe level as per 110.9 ,10 and 110.22. Add this to Sheet E9-0. 2. Indicate on Sheet E1.0 the location of Main Service Disconnect. 3. Provide a Budget Lighting analysis per 2006 IECC, and indicate switching methods to be used. 4. Sheet E9-0, Equipment Schedule, roll up door listed as 460 volts 3 phase ? Ray T Majuta Electrical Plan Review PDSD, City of Tucson 7/16/2012 Ray.Majuta@tucsonaz.gov |