Permit Number: T12CM03499
Parcel: 137055270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03499
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2012 TERRY STEVENS ZONING REVIEW Approved
06/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the sequence of operation for the restroom exhaust fan in the men's restroom so that all of the air supplied to the restroom will be exhausted (i.e. exhaust shall continue even if the lights are off). Reference: Section 403.2.1 (4), IMC 2006.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
06/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/14/2012 ROBERT SHERRY WATER REVIEW Approved
06/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
06/14/2012 JASON GREEN ENGINEERING REVIEW Approved
06/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/14/2012 MARTIN BROWN FIRE REVIEW Approved
06/14/2012 ERIC NEWCOMB ADA REVIEW Passed
06/14/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
06/20/2012 GERRY KOZIOL WWM REVIEW Approved