Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03499
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
06/14/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the sequence of operation for the restroom exhaust fan in the men's restroom so that all of the air supplied to the restroom will be exhausted (i.e. exhaust shall continue even if the lights are off). Reference: Section 403.2.1 (4), IMC 2006. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
06/14/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
06/14/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/14/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
06/14/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
06/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/14/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/14/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
06/14/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
06/20/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |