| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12cm03495 7290 E Tanque Verde Rd Sports Field Lighting 1,2 1. The 4-350MCM service entrance conductors are rate for 310 amps under the 2005 NEC,310.16 table, the Main is listed at 400 amps, 240.6 list the next size at 350 amps ? 2. Sheet E601 shows a 75KVA transformer being fed from Panel L2, Sheet E602 shows a 45KVA transformer in Panel L2 ? Ray T Majuta PDSD, C of Tuc Elect Plan Review 7/11/2012 Ray.Majuta@tucsonaz.gov |