Permit Number: T12CM03444
Parcel: 11711102A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03444
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2012 CPIERCE1 WATER REVIEW Needs Review
07/03/2012 CPIERCE1 FIRE REVIEW Needs Review
07/18/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Reilly Craft Pizza - Expansion - Beer Garden
T12CM03444
Building Plan (1st Review)

TRANSMITTAL DATE: July 23, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Based on a prior patio, use area, expansion of 1,250 sq. ft. and the proposed expansion of use into an existing garage of 1,258 sq. ft. the cumulatively expansion, 49.6% is greater than 25%. Provide an expansion calculation on the plan.

3. As an expansion of use is proposed provide a site plan that meets the requirements of D.S. 2-01.0.

4. Either a Development Review Board (DRB), LUC Section 2.8.10.4, or a Downtown Infill Incentive District (IID), LUC Section 2.8.12, review is required prior to approval of the site and building plans. Contact Russlyn Wells @837-4948 for DRB review requirements.

5. Historic review is required for this project prior to approval of the site and building plans. Contact Frank Podgorski @837-4962 for historic review requirements.

6. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
07/18/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A0.2
1. Exits: As per Table 1015.1, two exits are required for an occupancy load more than 49. Please change your required exits to "2".
2. The EXIT PLAN is incorrect and incomplete. Please provide an all encompassing exiting plan showing occupant load exit from the Beer Garage to the patio area, the two exits from the restaurant through the patio area and Show those loads combined exiting out the two courtyard exits metal panel gates. Also show the load exiting out the two building exits of the restaurant and the Beer Garage.
a. Show total occupancy loads of all uses in the restaurant dining, bar, kitchen, basement areas and courtyard seating occupancy.
SHEET A1.0
3. Show the steel panel fencing and exit gates correctly.
a. Insure all gates have panic hardware.
SHEET S1.1
4. Provide completed Certification Form for special inspectors as required by the 2006 IBC.

END OF REVIEW
07/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout sized per Section 708.7, IPC 2006 for the existing 4" building drain.
2. Show the proposed floor cleanouts (on plumbing floor plan) on the riser diagram.
07/26/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/01/2012 GERRY KOZIOL WWM REVIEW Approved