Permit Number: T12CM03380
Parcel: 10511061R

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM03380
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/15/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified water heater (Ariston GL2.5) is a storage-type water heater. Provide discharge piping for the temperature/pressure relief valve per Section 504.5, IPC 2006. Provide a means of controlling thermal expansion (e.g. a thermal expansion tank) per Section 607.3, IPC 2006.
2. Provide a means of limiting the hot water temperature per Section 416.5, IPC 2006. The specified valve (Watts L70) is not listed for this use.
06/19/2012 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2012 CPIERCE1 OUT TO CUSTOMER Completed