Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM03380
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03380
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2; SHEET A.7: LOCATE THE VERTICAL GRAB BAR PER THE ICC/ANSI A117.1-2003 FIGURE 604.5.1.
2. PREVIOUS COMMENT 3; SHEET A.8; DETAIL 2: PROVIDE THE BRACING SIZE AND CONNECTION TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE.
06/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the size of the sanitary waste from the lavatory as shown on the riser diagram (the plumbing plan shows the orrect size - 2").
2. Provide specifications and listing information for the water heater.
3. Provide specifications and listing information for the mixing valve. State that the valve will limit the water temperature to 110 degrees Fahrenheit or less. The valve shall be third-party listed to ASSE 1070.
06/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/14/2012 CPIERCE1 WWM REVIEW Needs Review