Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03380
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/13/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 2; SHEET A.7: LOCATE THE VERTICAL GRAB BAR PER THE ICC/ANSI A117.1-2003 FIGURE 604.5.1. 2. PREVIOUS COMMENT 3; SHEET A.8; DETAIL 2: PROVIDE THE BRACING SIZE AND CONNECTION TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE. |
06/13/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct the size of the sanitary waste from the lavatory as shown on the riser diagram (the plumbing plan shows the orrect size - 2"). 2. Provide specifications and listing information for the water heater. 3. Provide specifications and listing information for the mixing valve. State that the valve will limit the water temperature to 110 degrees Fahrenheit or less. The valve shall be third-party listed to ASSE 1070. |
06/13/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/13/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/14/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |