Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM03380
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03380
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
06/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed.
2, Provide a mechanical plan.
06/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03390
4500 N Oracle Rd
Pandora TI

Provide 2006 IECC Budget $ Lighting Calculations and show compliance with switching as required .Com-Check ok.
Date Electrical Plans as when sealed , as required by Arizona State.

Ray T Majuta
Electrical Plan Review
PDSD, City of Tucson
6/11/2012
Ray.Majuta@tucsonaz.gov
06/11/2012 ROBERT SHERRY WATER REVIEW Approved
06/11/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T.1; APPLICABLE CODES: ACCESSIBILITY IS PER THE ICC/ANSI A117.1-2003. REVISE NOTE.
2. SHEET A.7; RESTROOM ELEVATIONS: ADD VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003 FIGURE 604.5.1.
3. SHEET A.8; DETAIL 2: PROVIDE THE SIZE OF THE WALL BRACING AND THE CONNECTION OF THE BRACING TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE.
4. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/11/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
06/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed.
2, Provide a plumbing plan.
06/11/2012 KEN BROUILLETTE FIRE REVIEW Approved
06/11/2012 ERIC NEWCOMB ADA REVIEW Passed
06/11/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/13/2012 CPIERCE1 WWM REVIEW Needs Review