Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03380
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/11/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/11/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed. 2, Provide a mechanical plan. |
06/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03390 4500 N Oracle Rd Pandora TI Provide 2006 IECC Budget $ Lighting Calculations and show compliance with switching as required .Com-Check ok. Date Electrical Plans as when sealed , as required by Arizona State. Ray T Majuta Electrical Plan Review PDSD, City of Tucson 6/11/2012 Ray.Majuta@tucsonaz.gov |
06/11/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/11/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T.1; APPLICABLE CODES: ACCESSIBILITY IS PER THE ICC/ANSI A117.1-2003. REVISE NOTE. 2. SHEET A.7; RESTROOM ELEVATIONS: ADD VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003 FIGURE 604.5.1. 3. SHEET A.8; DETAIL 2: PROVIDE THE SIZE OF THE WALL BRACING AND THE CONNECTION OF THE BRACING TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE. 4. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
06/11/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
06/11/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed. 2, Provide a plumbing plan. |
06/11/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
06/11/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
06/11/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/13/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |