Permit Number: T12CM03331
Parcel: 13313005F

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM03331
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied No structural calculations provided to show capability of existing roofs to handle the additional dead loads.

No structural layout for panels on existing roofs. Please show type of ballasts, location of ballasts, number of ballasts used in each area, locacation of standoffs, etc.

Provide plan sheets showing connection details for solar panels to carport roofs.

Page L 1.0 project narrative is inaccurate. Please delete or revise.
06/25/2012 KEN BROUILLETTE FIRE REVIEW Approved
06/25/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2012 CPIERCE1 OUT TO CUSTOMER Completed