Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T12CM03331
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/07/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 06/18/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/18/2012 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | No structural calculations provided for showing capability of existing roofs to handle the additional dead loads. No structural layout for panels on existing roofs. Please show type of ballasts, location of ballasts, number of ballasts used in each area, locacation of standoffs, etc. Provide plan sheets showing connection details for solar panels to carport roofs. Page L 1.0 project narrative is inaccurate. Please delete or revise. |
| 06/18/2012 | LHANLY1 | ADA | REVIEW | Approved | |
| 06/18/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review |