Permit Number: T12CM03281
Parcel: 125042410

Address:
2124 E 2ND ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM03281
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM03281
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FLOOR PLANS:

1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1.
2. Show window sizes for determining compliance with R310 providing egress from the basement. The basement requires one operable emergency escape and rescue opening.

ELECTRICAL PLANS:

1. A wall switch for illuminating stairs must be provided at each floor level of stairways including the basement, R303.6.1.
2. Show all receptacle outlets in unfinished basements with ground fault circuit interrupting protection. Label each receptacle GFCI requiring such protection, E3802.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
11/14/2012 CAGUILA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2012 CINDY AGUILAR OUT TO CUSTOMER Completed