Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03263
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the sequence of operation for the restroom exhaust fans so that the fans operate whenever HVAC air is supplied to the restrooms. 2. Clarify the location of the duct smoke detector for HP-2 (upstream of filters and outside air) and show the location of the audible and visual alarms. |
| 06/06/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/06/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/06/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Need structural evaluation ofthe new HVAC roof top mounted ubnits. 2. Need structural calculations for new wall bracket mounted 120 gallon water heater plus wall evaluation. END OF REVIEW |
| 06/06/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify how the water heater support is to be "attached in an approved manner". 2. Show how the water heater can be removed for maintenance or replacement without modifying the building structure. |
| 06/06/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 06/06/2012 | RONALD BROWN | ADA | REVIEW | Passed | |
| 06/06/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/07/2012 | CAGUILA1 | WWM | REVIEW | Needs Review |