Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03263
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
06/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the sequence of operation for the restroom exhaust fans so that the fans operate whenever HVAC air is supplied to the restrooms.
2. Clarify the location of the duct smoke detector for HP-2 (upstream of filters and outside air) and show the location of the audible and visual alarms.
06/06/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/06/2012 ROBERT SHERRY WATER REVIEW Approved
06/06/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need structural evaluation ofthe new HVAC roof top mounted ubnits.
2. Need structural calculations for new wall bracket mounted 120 gallon water heater plus wall evaluation.
END OF REVIEW
06/06/2012 JASON GREEN ENGINEERING REVIEW Approved
06/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify how the water heater support is to be "attached in an approved manner".
2. Show how the water heater can be removed for maintenance or replacement without modifying the building structure.
06/06/2012 KEN BROUILLETTE FIRE REVIEW Approved
06/06/2012 RONALD BROWN ADA REVIEW Passed
06/06/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/07/2012 CAGUILA1 WWM REVIEW Needs Review