Permit Number: T12CM03204
Parcel: 110082450

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03204
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need to provide accessible parking space.
2. Need to prrovide accessible route and entry to front door.
3. Need to provide structural calculations for the foundation and roof framing of the new additions.
4. Need to provide structural calculations for all root top mounted HVAC equipment.
5. Please identify the accessible bedroom.
6. The bathroom identified as the accessible bathroom is not compliant. Please redesign to meet all requirements of ICC A117.1, Section 1003.11; Type "A" Toilet and Bath Facilities.
END OF REVIEW
07/24/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/25/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
07/25/2012 CPIERCE1 WWM REVIEW Needs Review
07/25/2012 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/25/2012 CPIERCE1 WATER REVIEW Needs Review
07/25/2012 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review