Permit Number: T12CM03183
Parcel: 13413057S

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM03183
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/04/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/04/2012 JASON GREEN ENGINEERING REVIEW Approved
06/04/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the velocity in the grease exhaust duct to a minimum of 1500 FPM
2. Show how the hood is to be supported from the building structure.
06/04/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond NEW HOOD SUPPRESSION PERMIT REQUIRED FOR NEW HOOD
06/04/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
06/04/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
06/04/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/08/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed