Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM03183
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/04/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/04/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/04/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the velocity in the grease exhaust duct to a minimum of 1500 FPM 2. Show how the hood is to be supported from the building structure. |
| 06/04/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | NEW HOOD SUPPRESSION PERMIT REQUIRED FOR NEW HOOD |
| 06/04/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/04/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/04/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/08/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |