08/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03121
1880 E Irvington, Walgreens

These items have to do with the corrections for last review.


1. According to NEC 2005 220.87, Determining Existing Loads, the maximum demand date available for a one year
period is required. Sheet E610 indicates under the "Existing Service Demand" a Peak Demand from Utility Bills. Provide
the one year period of time date taken.
2. Article 220.87 also indicates that the max demand at 125% to be added to the new load.
3. How was the "Current with Diversity " of 418.5 Amps determined ? This was also shown on Sheet E610.

Ray T Majuta
Elect Pln CK
DPD of City of Tucson
8/14/2012