Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM03121
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/13/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03121 1880 E Irvington, Walgreens These items have to do with the corrections for last review. 1. According to NEC 2005 220.87, Determining Existing Loads, the maximum demand date available for a one year period is required. Sheet E610 indicates under the "Existing Service Demand" a Peak Demand from Utility Bills. Provide the one year period of time date taken. 2. Article 220.87 also indicates that the max demand at 125% to be added to the new load. 3. How was the "Current with Diversity " of 418.5 Amps determined ? This was also shown on Sheet E610. Ray T Majuta Elect Pln CK DPD of City of Tucson 8/14/2012 Ray>Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/21/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |