Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03121
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/04/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/08/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/15/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the basis for the ventilation calculations. The "zone & area" designations do not correspond to the room names on the floor plans - is this calculation for this building? Reference: Sections 106.3.1 and 403.3, IMC 2006. 2. The ventilation calculations appear to be based on ASHRAE 62.1 but they do not include sufficient information to be evaluated for a multiple-zone system. Provide the zone air distribution effectiveness (Section 6.2.2.2, ASHRAE 62.1-2004) and the calculations called for in Section 6.2.5, ASHRAE 62.1-2004. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
| 06/15/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Remove unused details from the drawing set (e.g. details 2, 3, and 5/P-610) or clearly indicate where they apply. Reference: Section 106.3.1, IPC 2006. 2. Coordinate the power requirements of the tankless water heaters with the electrical drawings. Reference: Section 303.2, IPC 2006. 3. Revise the design of the venting for the new floor sinks so that the vents rise vertically to at least 6" above the flood rim of the fixture being served prior to running horizontally. Reference: Section 905.4, IPC 2006. |
| 06/15/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/19/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 06/25/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03121 1880 E Irvington Rd Walgreens TI 1. Cannot not find any information on Mechanical Sheets for C-1 and C-2 units,specifications cut sheet to be provided. 2.The EWH-1 shows a 20 gal,115 v,4.5 kw load, the panel schedule shows a 3.6 kw load on a 20 amp circuit ? 3.Sheet E-121 note 26-50-42 indicates to provide a circuit to connect these fixtures,contractor to install. Provide a circuit to connect these. 4.Sheet E-131, circuits LPSP- 2,10 how were the loads determined for these ? 5. Provide a circuit for light on note 26 50 35. 6.Sheet E-610 note 5, are panel boards to be replaced or just revised loads ? 7.Per City of Tucson TI requirements, provide the total wattage or va and amps per phase on each panel. Also provide the new total load for the service. Ray T Majuta Electrical Plan Review PDSD, C of Tucson 6/25/2012 Ray.Majuta@tucsonaz.gov |
| 06/28/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |