Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM03117
Parcel: 12306096B

Address:
2134 E ADAMS ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM03117
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
07/13/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 7-13-12
Activity: T12CM03117 2nd review
Address: 2134 E Adams
Applicant: Bill Taylor

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

OUTDOOR LIGHTING CODE
1. Previous comment: Provide cut sheets for all exterior lighting fixtures showing the angle of cutoff, light emissions and fixture wattage.
The cut sheet provided for the motion lights specifies that the fixture takes (2) 120 watt bulbs. Typical bulbs of that size and type average 1800 lumens each.
(1800 lumens each x 2 bulbs x 6 fixtures = 21,600 lumens).
The allowable unshielded lumen limit for the property has been exceeded. Show compliance with the Pima County Outdoor Lighting Code.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review