Permit Number: T12CM03117
Parcel: 12306096B

Address:
2134 E ADAMS ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM03117
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2012 MICHAEL ST. PAUL ZONING REVIEW Denied Site OK. DDO in process. DDO approval is required. See DDO comments with first review.
06/08/2012 MARTIN BROWN FIRE REVIEW Approved
06/20/2012 GERRY KOZIOL WWM REVIEW Approved
06/22/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 6-27-12
Activity: T12CM03117
Address: 2134 E Adams
Applicant: Bill Taylor

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide sheets A700 and A701 for review.
2. Correct sheet index for sheet S302 labeled A302.

STRUCTURAL / FRAMING PLAN:
3. Specify header size over living room window.
4. Specify length of all braced wall panels.
5. Tributary areas in structural analysis do not match building dimensions.
6. Provide consistent information between structural calculations and section detail regarding the required reinforcement in the concrete tilt-up panel.

SECTIONS - DETAILS:
7. Specify all ledger connections to masonry walls with minimum 3x ledger materials, Figure R606.11(1).
8. Correct detail title 'Not Used' for details 10 and 19.
9. Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.

PLUMBING PLAN:
10. Two-way cleanout required within 2' from the building at the lower end, P3005.2.
11. Minimum ¾" gas line is required from the meter to the first log lighter branch for the proposed distance and demand.

ELECTRICAL PLAN:
12. Provide a 20-amp circuit to serve laundry circuit, E3603.3, 3801.8.

OUTDOOR LIGHTING CODE
13. Provide cut sheets for all exterior lighting fixtures showing the angle of cutoff, light emissions and fixture wattage.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2012 CINDY AGUILAR OUT TO CUSTOMER Completed