Permit Number: T12CM03084
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03084
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2012 DAVID RIVERA ZONING REVIEW Approved
06/11/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide most current Site Plan.
SHEETS A1 AND A2
2. At door 13, please provide a large scale detail of the entire ramp system showing all accessibility requirements,; slopes, lengths, landings, dimensions and handrails. Please show how existing handrails meet the new handrails.
a. Please provide a large scale handrail elevation showing existing and new.
END OF REVIEW
06/12/2012 ROBERT SHERRY WATER REVIEW Approved
06/12/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing plan with the soil and vent diagram; the plumbing plan shows a 3" building drain but the diagram shows a 4" building drain. Reference: Section 106.3.1, IPC 2006.
2. Coordinate the design for the water heater mounting shelf with architectural detail 3/A3. Verify that there is adequate space for installation and maintenance access for the water heater and its accessories. Reference: Sections 106.3.1, 301.2, and 501.4 IPC 2006.
3. Provide a vacuum relief valve for the specified, bottom-feed, storage-type water heater. Reference: Section 504.2, IPC 2006.
06/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2006.
2. Provide justification for not providing ventilation for the IT Room but supplying ventilation for the storage room. Reference: Section 403.3, IMC 2006.
06/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/18/2012 GERRY KOZIOL WWM REVIEW Approved