06/20/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM03053
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FOUNDATION PLANS:

1. Identify the size and structural reinforcement of F-3 shown on S1.0.
2. Indicate the slope for garage slab, R309.3.
3. Show compliance with termite treatment, R320.

FLOOR PLANS:

1. Show a floor plan labeling all proposed functions of rooms and spaces, R106.1.1.

SECTIONS - DETAILS:

1. Clarify the scale shown on the "New Plan" sheet A1.1, R106.1.1.
2. Clarify the 1/S3.2 schedule referenced on Detail 8/S2.1, R106.1.1.

PLUMBING PLANS:

1. Show plumbing vent (VTR) sizes within acceptable distances from traps, P3111.3.
2. The 2" RV Dump drain is undersized for a typical 4" drain hose.

ELECTRICAL PLANS:

1. Show all readily accessible garage receptacle outlets with GFCI protection, E3802.2. Include adjacent rooms.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1. Show component values on the plans for conditioned locations.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
06/21/2012 MARTIN BROWN FIRE REVIEW Approved Fire flow required for this struture is 2,250 GPM. Records indicate 4,415 GPM available (@ 20 psi). No fire sprinklers required.
06/22/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET S1
1. Foundation Plan: Provide F3 footing on footing schedule and reference proper detail.
2. Need to provide Special Inspectors certification for 3,500 psi concrete.
3. Framing Plan: Detail 6/S2.2 is not representative of the actual conditions. Please redesign detail as to actual conditions configuration.
SHEETS S2.1 AND S2.2
4. Please delete all details that are not pertinent to this project and reference all those details that are pertinent from the foundation and framing plans.
END OF REVIEW
07/06/2012 GERRY KOZIOL WWM REVIEW Denied SEPTIC REVIEW - WARREN 740-6490

Final Status

Task End Date Reviewer's Name Type of Review Description
07/10/2012 CINDY AGUILAR OUT TO CUSTOMER Completed