Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM03051
Parcel: 138241630

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM03051
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2012 MARTIN BROWN FIRE REVIEW Approved
06/04/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide a letter of deferred submittals to the building official, Mr. Ron Boose for the wood trusses.
SHEET A1
2. Can not have two unisex toilets for public rooms. Please reference the 2006 IBC, Sections 1109.2.1, 2902.2, .3, and ,.4.
3. Please show accessible seating as required by the 2006 IBC, Sections 1109.11 and ICC A117.1, Section 902 on the drawings.
4. As per your exiting calculations, only one exit is required. Your occupant exiting plan detailon A3 shows 3 exits. As per section 1014.2.1, egress shall not pass through a storage room or kitchen. Please rework your exiting plan.
5. Please change your ADA signage details to that required by the ICC A117.1, Section 703.
6. Please provide soils report and redesign foundations for the canopy foundations being placed in the Erosion Hazard Setback as required by Engineering. Reference engineering comments.
END OF REVIEW
06/05/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
06/12/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Reconcile the two different roof designs shown on the architectural and the structural drawings for roof slope and direction of slope. Reference: Section 103.2.3, UPC 2006.
2. Appliances (e.g. auto-fill units, ice makers, chemical dispensers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
3. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. a 2" cleanout is too small to serve a 3" waste pipe).
4. Provide a reduced pressure principle backflow preventer for the water supply to a carbonator. Reference: Section 603.4.12, UPC 2006.
5. Revise the design of the floor drain in the walk-in cooler to have an indirect connection per Section 801.2.2, UPC 2006.
6. Provide information to show that the proposed hydromechanical grease interceptor includes an integral flow control device (an "in-line" flow control device is not necessarily an integral flow control device). If not, install a vented, external flow control device per the manufacturer's instructions in a readily accessible and visible location. Reference: Section 1014.2.1, UPC 2006.
7. A vent for a hydromechanical grease interceptor shall be located downstream of the interceptor and no system vents shall be located between the flow control device and the interceptor. Reference: Sections 1014.2.1 and 1014.2.3, UPC 2006.
8. Revise the size of the scupper for the main roof area to comply with the requirements of Section 1101.11.2.1, UPC 2006. Refer also to Section 1106.4, UPC 2006.
06/12/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the submitted energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet (the town of Pima, Arizona is in Graham County). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information on the drawing shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Coordinate the drawings with the calculations (e.g. the drawings show the roof with R-38 cavity insulation and no continuous insulation but the calculations show R-30 cavity insulation with R-1.5 continuous insulation). Sign the energy calculations. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Show how the water-cooled soft-serve machines (i.e. equipment numbers 2B, 2E, and 5C) comply with the requirements of Section 1201.3, IMC 2006, as amended by the City of Tucson.
3. Clarify the installation requirements for the glycol fluid cooler shown on sheets M.1 and P.1. Reference: Section 106.3.1, IMC 2006.
06/12/2012 DAVID RIVERA ZONING REVIEW Denied Zoning cannot approve the building plans until the Development Package is approved.
06/12/2012 ROBERT SHERRY WATER REVIEW Approved
06/15/2012 JASON GREEN ENGINEERING REVIEW Denied Building plan will be approved once all comments associated with DP12-0080 have been addressed and the DP Package is approved.
06/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03051
New Dairy Queen

1. Sheet E-1 cannot locate circuits A-31-33 on the power plan.
2. Sheet E-1 circuits A-25,27 for the water heater should be A-26,27.
3. Sheet E-3, the service entrance conductors from the utility to the building service need a fourth wire for the neutral in each set.
4. Sheet E-3, the ground system for the service shown as a #4 cu needs to be a #2 cu per 2005 NEC 250.66, since the feeders are parelled ( two sets) the 250 mcm's now =- 500 mcm requiring up-sizing the conductor.
5. Sheet E-1, NEC 2005 210.8.B.2 requires receptacles in a commercial kitchen to be GFCI protected.Provid a note to indicate this on the sheet.
6. Sheet E-3, cannot locate circuit A-8 as shown on the panel schedule.

Ray T Majuta
Elect Plan Review
PDSD City of Tucson
6/19/2012
06/23/2012 GERRY KOZIOL WWM REVIEW Denied 1. DAIRY QUEEN
2. CONNECTING TO ON SITE PRIVATE SEWER (4" HCS TO 8" PRIVATE SEWER) NEED PCRWRD/CHAD AMATEAU REVIEW OF LOCATION/METHOD OF CONNECTION TO PRIVATE SEWER INCLUDING REVIEW OF OWNERSHIP OF PRIVATE SEWER (JOINT USE & MAINTENANCE AGREEMENTS)
3. NEED WW/IWC REVIEW F.T. RUSTY RICCABONI JR 740-6200 3035 W EL CAMINO DEL CERRO

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed