Permit Number: T12CM02973
Parcel: 12710084B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM02973
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2012 TERRY STEVENS ZONING REVIEW Approved
05/24/2012 LOREN MAKUS ENGINEERING REVIEW Approved
05/24/2012 ERIC NEWCOMB ADA REVIEW Passed
05/24/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A3.0; ENLARGED RESTROOM PLAN 1; AT THE MEN'S RESTROOM URINAL, SINCE THE TOILET PARTITION IS GREATER THAN 24" IN LENGTH, THE CLEAR WIDTH FOR THE STALL MUST BE A MINIMUM OF 36" PER ICC/ANSI A117.1-2003, FIGURE 305.7(a).
2. SHEET A4.0; URINAL ELEVATION 2: SEE NOTE 1.
3. SHEET A4.0; ACCESSIBLE TOILET STALL: ADD A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.
4. SHEET A0.0; CODE ANALYSIS: THE OCCUPANCY CLASSIFICATION SHOULD BE A-2 (RESTAURANT) RATHER THAN THE B (BUSINESS) LISTED.
05/24/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/25/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/25/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Sections 102.4 and 106.3.1, IPC 2006.
2. Verify that a service sink is still available to comply with the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for an A2 (assembly) occupancy.
05/25/2012 ROBERT SHERRY WATER REVIEW Approved
05/25/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/29/2012 KEN BROUILLETTE FIRE REVIEW Approved
05/31/2012 CPIERCE1 WWM REVIEW Needs Review