Permit Number: T12CM02857
Parcel: 10510252A

Address:
4240 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM02857
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/09/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Note #3 for the Packaged AC Unit Schedule calls for duct smoke detectors to be installed per Section 606.2.1, IMC 2006 but in the supply duct. Per Section 606.2.1, smoke detectors are to be located in the return air duct, upstream of any outside air connections. The IMC does not require smoke detectors to be installed if the air handling units are not capable of distributing smoke-laden air beyond the enclosing walls of a single room or space where the smoke has been generated. Clarify your intent. Reference: Section 606.1, IMC 2006.
07/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/09/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/11/2012 FRODRIG2 ENGINEERING REVIEW Needs Review
07/11/2012 FRODRIG2 ZONING REVIEW Needs Review