Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T12CM02857
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/09/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/09/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Note #3 for the Packaged AC Unit Schedule calls for duct smoke detectors to be installed per Section 606.2.1, IMC 2006 but in the supply duct. Per Section 606.2.1, smoke detectors are to be located in the return air duct, upstream of any outside air connections. The IMC does not require smoke detectors to be installed if the air handling units are not capable of distributing smoke-laden air beyond the enclosing walls of a single room or space where the smoke has been generated. Clarify your intent. Reference: Section 606.1, IMC 2006. |
| 07/09/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/09/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/11/2012 | FRODRIG2 | ENGINEERING | REVIEW | Needs Review | |
| 07/11/2012 | FRODRIG2 | ZONING | REVIEW | Needs Review |