Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T12CM02847
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 05/21/2012 | ANY | WWM | REVIEW | Active | |
| 05/21/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 05/21/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/21/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 05/21/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/21/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/21/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/06/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Active | 1. Clarify how the water heater support is to be "attached in an approved manner". 2. Show how the water heater can be removed for maintenance or replacement without modifying the building structure. |