Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM02845
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/21/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
| 05/21/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/21/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/21/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/21/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/21/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/21/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 05/21/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 05/21/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/01/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |