Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM02811
Parcel: 115044910

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T12CM02811
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied RFIs and BULLETIN references do not make as built drawings. All changes must be shown on the drawings. Please call LeeRay Hanly at 1-(520)-838-4906
10/04/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
10/04/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM02811
1020 N Tyndall Av
Tyndall Project


As-Built Drawings denied.
Provide a detailed report showing the following:
1. Identify the sheet modification has been made to
2. Give a short precise discription of the modifiaction
3. Reason modification made
4. If a substitution has been made, describe the type of material, equipment or other substituted
5. If modification involves another sheet indicate
6. Describe changes to clouded areas, explanation not provided for some
7. Remove all handwritten changes and provide accurate as-builts

As-Built changes are to be reviewed so as to be in compliance with code project reviewed under, this case the 2005 NEC.
Hand written items on approved plans to be removed and approved by EE of record or representative.

Other items of concern are as follows:
1. new circuits added to panels with no loads shown
2. fire dampers and smoke detectors added no loads, no information on tie into Fire Alarm Circuits
3. Light fixtures changed with no changes to IECC report
4. Sheet E-500 Fire Pump size changed, as hand written indication shows
5. Sheet E-502, large clouded area showing removed no information or explanation
6. Sheet E-503 to 510 have changes to panels schedules, handwritten, no loads
7.Sheet E-510 has entire SES-H calculations changed no explanation
8. Sheet E-510 has Distrubution Board clouded no explanation

This review may not include all revisions covered under as-builts, review all changed prior to resubmittal

Ray T Majuta
Elect Plan Review
PDSD, Tucson
10/4/2013
Ray.Majuta@tucsonaz.gov
520-837-4988
10/04/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2013 CPIERCE1 APPROVAL SHELF Completed
10/04/2013 CPIERCE1 OUT TO CUSTOMER Completed