Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T12CM02811
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S106A; SHEET NOTES: NEW NOTE 7 WAS NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET S106A; ROOF FRAMING PLAN: DETAILS 214, 215, 305, 307, 316 AND 317 ARE INCLUDED IN THE REVISION AREA. HAVE THESE DETAILS CHANGED FROM THE APPROVED SET? VERIFY.
3. SHEET S502; DETAILS 320, 321, 322, AND 323: NOTE 1 INDICATES "FOR DIRECTION OF DECK SEE PLANS". INDICATE THAT ON THE PLANS.
4. SHEET S502; DETAIL 319: PROVIDE A NOTE FOR THE STIRRUP SIZE AND SPACING AT THE TOP STAIR STEP.
5. SHEET S502; DETAIL 319 (NOTE 9): PROVIDE A CONNECTION OF THE ANGLE AT EACH END.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/12/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2013 CPIERCE1 REJECT SHELF Completed
12/14/2012 CPIERCE1 OUT TO CUSTOMER Completed