Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/05/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/05/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | SPECIAL INSPECTIONS FOR SMOKE CONTROL SHALL BE FOLLOWED PER 2006 IFC SECTION 909.18.8. |
11/14/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Coordinate the locations of the exhaust shafts and the routing of the exhaust ducts with the large-scale mechanical plans. In addition, clarify the location of exhaust shaft "D"; there appears to be one near column 6-E and another near column 8-E, and clarify the name of the exhaust shaft located near 1.8-C.5; it is labeled as "G" on the second floor and "J" on the third floor and floors 4-13. 2. Coordinate the drawings to show the continuation of the trash exhaust. [Original comment: Include the exhaust from the trash room with the detail of the exhaust shaft "D" on sheet M5.4.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/20/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
11/20/2012 | CINDY AGUILAR | REJECT SHELF | Completed |