Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM02811
Parcel: 115044910

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM02811
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/05/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond SPECIAL INSPECTIONS FOR SMOKE CONTROL SHALL BE FOLLOWED PER 2006 IFC SECTION 909.18.8.
11/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Coordinate the locations of the exhaust shafts and the routing of the exhaust ducts with the large-scale mechanical plans. In addition, clarify the location of exhaust shaft "D"; there appears to be one near column 6-E and another near column 8-E, and clarify the name of the exhaust shaft located near 1.8-C.5; it is labeled as "G" on the second floor and "J" on the third floor and floors 4-13.
2. Coordinate the drawings to show the continuation of the trash exhaust. [Original comment: Include the exhaust from the trash room with the detail of the exhaust shaft "D" on sheet M5.4.]

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2012 CINDY AGUILAR OUT TO CUSTOMER Completed
11/20/2012 CINDY AGUILAR REJECT SHELF Completed