Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM02811
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/06/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: SHEET A105 IS LISTED AS HAVING A DRAWING UPDATE (ADDED RATED SHAFT AT THE FITNESS RESTROOMS). THIS SHEET WAS NOT INCLUDED FOR REVIEW. PROVIDE. |
09/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
09/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify how each of the exhaust shafts served by EF-5 and EF-7 are able to have "continuous upward airflow to the outside" if the fire damper closes off the duct to the exhaust fans. Reference: Section 716.5.3, exception 2, IBC 2006 and Section 607.5.5, exception 2, IMC 2006. 2. Coordinate the size of the exhaust duct that runs from unit H through unit C to the exhaust shaft. Reference: Section 106.3.1, IMC 2006. 3. Coordinate the locations of the exhaust shafts and the routing of the exhaust ducts with the large-scale mechanical plans. In addition, clarify the location of exhaust shaft "D"; there appears to be one near column 6-E and another near column 8-E, and clarify the name of the exhaust shaft located near 1.8-C.5; it is labeled as "G" on the second floor and "J" on the third floor and floors 4-13. 4. Include the exhaust from the trash room with the detail of the exhaust shaft "D" on sheet M5.4 |
09/17/2012 | KEN BROUILLETTE | FIRE | REVIEW | Denied | Waiting for mechanical issues to be addressed. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/29/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |