Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: SHEET A105 IS LISTED AS HAVING A DRAWING UPDATE (ADDED RATED SHAFT AT THE FITNESS RESTROOMS). THIS SHEET WAS NOT INCLUDED FOR REVIEW. PROVIDE.
09/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify how each of the exhaust shafts served by EF-5 and EF-7 are able to have "continuous upward airflow to the outside" if the fire damper closes off the duct to the exhaust fans. Reference: Section 716.5.3, exception 2, IBC 2006 and Section 607.5.5, exception 2, IMC 2006.
2. Coordinate the size of the exhaust duct that runs from unit H through unit C to the exhaust shaft. Reference: Section 106.3.1, IMC 2006.
3. Coordinate the locations of the exhaust shafts and the routing of the exhaust ducts with the large-scale mechanical plans. In addition, clarify the location of exhaust shaft "D"; there appears to be one near column 6-E and another near column 8-E, and clarify the name of the exhaust shaft located near 1.8-C.5; it is labeled as "G" on the second floor and "J" on the third floor and floors 4-13.
4. Include the exhaust from the trash room with the detail of the exhaust shaft "D" on sheet M5.4
09/17/2012 KEN BROUILLETTE FIRE REVIEW Denied Waiting for mechanical issues to be addressed.