Permit Number: T12CM02794
Parcel: 133372590

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM02794
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2012 MARTIN BROWN FIRE REVIEW Approved
06/06/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 1 (BRIDGE DRAWINGS); GENERAL NOTES: A GEOTECHNICAL REPORT IS REFERENCED FOR ALLOWABLE SOIL PRESSURES AND REQUIREMENTS. PROVIDE THAT REPORT FOR REVIEW.
2. SHEET 1 (BRIDGE DRAWINGS); SECTION D: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE '2" CLEAR' CALL-OUT (THREE LOCATIONS) AND THE '3" CLEAR' CALL-OUT (ONE LOCATION).
06/13/2012 PAUL MACHADO ENGINEERING REVIEW Approv-Cond Permit is for bridge structure only and cond-approval is dependant upon the recordation of a ped./maint./slope easement for the portion of the bridge abutment that is out of the 6' PUE. PM. 06-13-12.
06/13/2012 FRODRIG2 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed