Permit Number - T12CM02769
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The code analysis on sheet A0.1 indicates that this activity has been designed per the 2006 UPC. This review is for the underground plumbing only. 2. Provide protecting vents for all traps. 3. "Sureseal" trap protectors are not approved as the sole method for protecting the water seal of traps. A listed trap primer or a hose bibb located in the same room as the trap are acceptable methods for protecting seldom-used traps. |
| 05/21/2012 | FRODRIG2 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/21/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |