Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/20/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; the ¾" branch pipe serving the urinal will have a velocity exceeding 8 FPS. [Original comment: The branch piping sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.]
07/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM02746
6720 S Alvernon
Office and Warehouse TI

1. Last review requested 2006 IECC Lighting Budget Compliance Report, ------ not provided.
2. Last review requested a Fault Current Summary Report, -------not provided.
3. Sheet E2.1, please connect emergency fixtures to circuits, note on sheet leaves connection up to contractor.


Ray T Majuta
Electrical Pln Review
PDSD, C of Tucson
7/27/2012