Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM02746
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/20/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/23/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; the ¾" branch pipe serving the urinal will have a velocity exceeding 8 FPS. [Original comment: The branch piping sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.] |
| 07/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM02746 6720 S Alvernon Office and Warehouse TI 1. Last review requested 2006 IECC Lighting Budget Compliance Report, ------ not provided. 2. Last review requested a Fault Current Summary Report, -------not provided. 3. Sheet E2.1, please connect emergency fixtures to circuits, note on sheet leaves connection up to contractor. Ray T Majuta Electrical Pln Review PDSD, C of Tucson 7/27/2012 Ray.Majuta@tucsonaz.gov |