Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM02746
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A0.1; DRAWING LIST: THIS IS THE SAME SET USED FOR THE SHELL PERMIT. REMOVE ALL DRAWINGS FROM THE LIST THAT ARE NOT USED FOR THIS TENANT IMPROVEMENT. 2. SHEET A0.1: REMOVE CLOUDS FROM THIS SHEET. THOSE ARE FOR REVISIONS TO THE SHELL PERMIT. 3. SHEET A0.1; CODE INFORMATION: THE PROJECT DESCRIPTION SHOULD BE REVISED FOR THIS TENANT IMPROVEMENT. 4. SHEET A2.1; FLOOR PLAN: A NOTE NEAR GRIDS 4 AND B INDICATES TO "SEE STRUCTURAL". PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO STRUCTURAL SHEETS), OR REMOVE/REVISE NOTE. 5. SHEET A2.1: REMOVE CLOUDS FROM THIS SHEET. THOSE ARE FOR REVISIONS TO THE SHELL PERMIT. 6. SHEET A2.1; DETAIL 4: A NOTE REFERENCES TO "SEE CIVIL" FOR THE CONCRETE STOOP. PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO CIVIL SHEETS), OR REMOVE/REVISE NOTE. 7. SHEET A2.1; DETAIL 5: A NOTE REFERENCES TO "SEE CIVIL" FOR THE CONCRETE SIDEWALK AND RETAINING WALL. PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO CIVIL SHEETS), OR REMOVE/REVISE NOTES. 8. SHEET A2.1; DETAIL 5: A DETAIL CUT 3/A2.1 SIM THROUGH THE STAIR IS INDICATED. IS THIS CORRECT? VERIFY. 9. SHEET A2.1; FLOOR PLAN: CUT SECTION 5/A2.1 ON THE PLAN, OR ADD REFERENCE TO SHEET A2.2. 10. SHEET A2.1; PLAN 6: A NOTE REFERENCES TO "SEE CIVIL" FOR THE TOP OF CONCRETE. PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO CIVIL SHEETS), OR REMOVE/REVISE NOTE. 11. SHEET A2.1; SECTION 7: A NOTE REFERENCES TO "SEE CIVIL" FOR THE PAVING. PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO CIVIL SHEETS), OR REMOVE/REVISE NOTE. 12. SHEET A2.1 (SECTION 5); SHEET A2.2 (ELEVATION 5): COORDINATE THE CONFIGURATION OF SECTION 5 AND ELEVATION 5 (STAIR, FOUNDATION, HANDRAIL, ETC). 13. SHEET A2.2: REMOVE CLOUDS FROM THIS SHEET. THOSE ARE FOR REVISIONS TO THE SHELL PERMIT. 14. SHEET A2.2; ELEVATION 5: NOTES REFERENCE TO "SEE CIVIL" FOR VARIOUS ELEMENTS. PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO CIVIL SHEETS), OR REMOVE/REVISE NOTES. 15. SHEET A2.2; OFFICE PLAN: NOTES REFERENCE TO "SEE CIVIL" FOR VARIOUS ELEMENTS. PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO CIVIL SHEETS), OR REMOVE/REVISE NOTES. 16. SHEET A2.2 (PLAN GENERAL NOTES); SHEET A9.2 (PARTITION TYPE 2): NOTE ONE IN THE GENERAL NOTES INDICATES ALL PARTITIONS TO BE TYPE 2A/TA UNLESS OTHERWISE NOTED. PARTITION TYPE 2A ON SHEET A9.2 INDICATES 6" METAL STUDS AT 12" 0C. IS THIS CORRECT? VERIFY (ADD WALL TYPE INDICATOR TO THE INTERIOR WALLS). 17. SHEET A2.1: REMOVE CLOUDS FROM THIS SHEET. THOSE ARE FOR REVISIONS TO THE SHELL PERMIT. 18. SHEET A2.3; DETAILS 2, 4, AND 5: NOTES REFERENCE TO "SEE STRUCTURAL" FOR VARIOUS ELEMENTS. PROVIDE INFORMATION ON THIS SET OF PLANS (THERE ARE NO STRUCTURAL SHEETS), OR REMOVE/REVISE NOTES. 19. SHEETS A2.3 AND A3.1: IS THERE ANYTHING ON THESE SHEETS THAT PERTAIN TO THE TENANT IMPROVEMENT? REMOVE SHEETS OR PORTIONS OF SHEETS AS REQUIRED. 20. SHEET A4.1: REMOVE CLOUDS FROM THIS SHEET. THOSE ARE FOR REVISIONS TO THE SHELL PERMIT. 21. SHEET A8.1: REMOVE CLOUDS FROM THIS SHEET. THOSE ARE FOR REVISIONS TO THE SHELL PERMIT. 22. SHEETS A8.1 AND A8.2: IS THERE ANYTHING ON THESE SHEETS THAT PERTAIN TO THE TENANT IMPROVEMENT? REMOVE SHEETS OR PORTIONS OF SHEETS AS REQUIRED. 23. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/22/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/23/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 06/07/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the design of the drain and vent piping to coordinate with the previously approved "foundation-only" plans. Reference: Section 103.2.3, UPC 2006. 2. Coordinate the water service with the previously approved civil drawings; the water meter and its backflow preventer are not located within the building. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf 3. Provide listing information for the water-tempering unit serving the emergency eyewash/shower. Reference: Section 301.1.1, UPC 2006. 4. Show the eyewash portion of the emergency eyewash/shower connected to the sanitary drain system. Reference: Section 304.0, UPC 2006. 5. Show the location of the termination for the direct vent system for the water heater and provide a copy of the manufacturer's installation instructions. Reference: Sections 103.2.3 and 512.0, UPC 2006. 6. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference: Sections 103.2.3, 605.5, and 608.3, UPC 2006. 7. The branch piping sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 8. Revise the rain gutter sizing (see Roof General Note 15/A2.3) based on a storm of 60-minutes duration and a 100-year return period, i.e. 3" per hour. Reference: Section 1106.3 and Table 11-3, UPC 2006. 9. Clarify the size of the overflow scuppers for the entry canopy. Reference: Section 1101.11.2.1, UPC 2006. 10. Provide a fixture description for roof drain, RD-1. Reference: Sections 103.2.3 and 1105.1, UPC 2006. 11. Revise the natural gas piping system; coordinate the connected loads with the mechanical design and the show the developed lengths from the meter to each gas-fired appliance. Reference: Sections 103.2.3, 1209.1.1, and 1209.1.2, UPC 2006. |
| 06/07/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/08/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. |
| 06/13/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | Conditions of Approval Permits where the sewer has yet been constructed or accepted by RWRD shall be issued without requiring a hold harmless letter and as follows: " Condition WW005 shall be placed on permit: " **NOTICE*** THE PUBLIC SANITARY SEWER TO WHICH THIS BUILDING INTENDS TO CONNECT HAS EITHER NOT COMPLETED CONSTRUCTION OR HAS NOT BEEN ACCEPTED BY REGIONAL WASTEWATER RELCAMATION DEPARTMENT. IT IS STRICTLY THE RESPONSIBILITY OF THE OWNER AND PERSON DOING THE WORK TO ENSURE THAT THE PUBLIC SEWER IS ACCEPTED PRIOR TO CONNECTION AND OCCUPYING THE BUILDING. NOTE THAT FINAL INSPECTIONS AND/OR CERTIFICATE OF OCCUPANCY SHALL NOT BE RELEASED PRIOR TO PUBLIC SEWER ACCEPTANCE. " A P2F shall be placed on residential projects " A P2C shall be placed on commercial projects |
| 06/13/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM02746 6720 S Alvernon TI Office Warehouse Electrical Plans denied , please address each item and show how addressed: 1.Provide 2006 IECC Budget Lighting Compliance Report, Com Check ok,include marked switching requirements. 2.Sheet E3.2, provide a Fault Current Summary Report beginning at Utility on through to panels and equipment. If a Series Rated System to be used provide a report describing the system to be used, to be printed on sheet . 3.Panel schedules are required to show individual phase loads and to be balanced to within 15% of each other. 4. Sheet E3.1 Grounding System for Service is showing use of aluminum, indicate how it will comply with 2005 NEC, 250.64.A. 5. Fire Pump Installation , if shown on plans requires all information provided with it as follows, cannot be subject to Installer: a. Provide full information such spec's sheets and equipment Identification concerning FPC,FP,JPC and JP. b. fault current listing and testing listing as OSHA on equipment noted on (a) above. c. verification of compliance with 2005 NEC 695.4.B.1 d. verification of compliance with 2005 NEC 695.6.A,B,C. e. Notate on Sheet E1.1, Installation of Fire Pump to comply with 2005 NEC 695 and NFPA 20. Ray T Majuta PDSD, City of Tucson Electrical Plan Review 6/14/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/06/2012 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |