Permit Number: T12CM02692
Parcel: 11008161A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM02692
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 7-06-12
Activity: T12CM02692 2nd review
Address: 4617 E Bermuda
Applicant: Lisa Duron

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide minimum 3/32" lettering per Development Standards or submit an appeal to the Building Official.

ELECTRICAL PLAN:
2. Bathrooms require a separate 20-amp circuit with receptacles within 3' of the basin, E3603.4, E3801.6. (Exterior receptacles may not share bath #1 circuit)

OUTDOOR LIGHTING CODE
3. The lumen allowance for this property has been exceeded. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2012 CPIERCE1 OUT TO CUSTOMER Completed