Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2012 GERRY KOZIOL WWM REVIEW Approved
06/12/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 6-13-12
Activity: T12CM02637
Address: 533 E Mabel St
Applicant: David Major

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Correct numbering for general notes sheet 3.
2. Correct code references for braced wall panels (Sheet 3- R602.103, R6023)
3. Compensate for venting in existing eave blocking covered with new roof structure.
4. UPC and IRC are not interchangeable codes. Correct all plumbing references sheet 5.
5. Duct insulation must be a minimum R-8 when located outside the thermal envelope, R1103.2.1.
6. All bedroom outlets shall be protected with combination-type arc-fault breakers (including receptacles, lights, and smoke detectors- circuits 11, 13), E3802.12.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2012 CPIERCE1 OUT TO CUSTOMER Completed