Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM02617
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 05/10/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/10/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 05/14/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 05/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/14/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/14/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |