Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM02578
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/20/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; the revised drawing shows the duct smoke detectors located downstream of the outside air connection. [Original comment: Revise the mechanical drawings to show the duct smoke detectors located upstream of any filters or outside air connections (the electrical power drawing shows duct smoke detectors located within the fan coils and note #4 on sheet M9.1 is incorrect). Reference: Section 606.2.1, IMC 2006.] |