Permit Number: T12CM02578
Parcel: 14027071A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM02578
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/20/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the revised drawing shows the duct smoke detectors located downstream of the outside air connection. [Original comment: Revise the mechanical drawings to show the duct smoke detectors located upstream of any filters or outside air connections (the electrical power drawing shows duct smoke detectors located within the fan coils and note #4 on sheet M9.1 is incorrect). Reference: Section 606.2.1, IMC 2006.]