Permit Number: T12CM02578
Parcel: 14027071A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM02578
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2012 MARTIN BROWN FIRE REVIEW Approved
05/16/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.0 (SITE PLAN); SHEET A1.0 (CODE INFORMATION): THE BUILDING ON THE SITE PLAN (ON SHEET A0.0) INDICATES THE TENANT IMPROVEMENT IS 2533 SF, WHILE THE CODE INFORMATION (ON SHEET A1.0) INDICATES A TENANT IMPROVEMENT AREA OF 4759 SF. CLARIFY.
2. SHEET A1.0; COMPOSITE PLAN: DARKEN THE LENGTH OF TRAVEL DISTANCES ON THE PLAN AND THE NUMBER OF OCCUPANTS EXITING THROUGH A DOOR ON THE PLAN.
3. SHEET A1.1 (FLOOR PLAN); SHEET A4.0 (BUILDING SECTIONS): THE PLAN INDICATES SECTION A/A4.0 EXTENDS FROM NORTH OF GRID 4 TO NORTH OF GRID 2, WHILE THE SECTION EXTENDS FROM GRID 1 TO NORTH OF GRID 4. REVISE.
4. SHEET A1.1 (FLOOR PLAN); SHEET A4.0 (BUILDING SECTIONS): THE PLAN INDICATES SECTION B/A4.0 EXTENDS FROM GRID C TO WEST OF GRID C, WHILE THE SECTION EXTENDS FROM WEST OF GRID B TO GRID C. REVISE.
5. SHEET A1.1 (FLOOR PLAN); SHEET A4.0 (BUILDING SECTIONS): THE PLAN INDICATES SECTION C/A4.0 EXTENDS FROM GRID C TO EAST OF GRID B, WHILE THE SECTION EXTENDS FROM GRID C TO WEST OF GRID B. REVISE.
6. SHEET A1.1; FLOOR PLAN: A SECTION CUT ON GRID LINE 4 INDICATES #/A6.0. REVISE.
7. SHEET A2.1; FLOOR PLAN: REVISE THE SECTION CUTS AND/OR SECTIONS TO MATCH PER PREVIOUS NOTES 3, 4, AND 5.
8. SHEET A4.0; BUILDING SECTION C: A NOTE 3 INDICATED IN THE NEW CLEAN ROOM IS INCORRECT. REVISE.
9. SHEET A4.0; BUILDING SECTION C: IS NOTE 17 INDICATED AT FOUR LOCATIONS IN THE NEW CLEAN ROOM CORRECT? VERIFY.
10. SHEET A4.1 (SECTIONS 4 AND 5); SHEET A6.0 (DETAIL 7): INDICATE ON A DETAIL HOW THE METAL STUD BRACING (DIAGONAL AND VERTICAL) IS CONNECTED TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE.
11. SHEET A4.1; SECTIONS 3 AND 5: PROVIDE BRACING FOR THE 3 5/8" METAL STUD WALL. INDICATE BRACING SIZE AND SPACING, AND ITS CONNECTION TO BOTH METAL STUD WALLS.
12. SHEET A4.2 (SECTION 1); DETAIL 2: INDICATE ON A DETAIL HOW THE METAL STUD BRACING (DIAGONAL AND VERTICAL) IS CONNECTED TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE.
13. SHEET A4.2; DETAIL 2: AT THE NOTE REFERENCE FOR THE BRACING TO THE ROOF, INDICATE THE SPECIFIC DETAIL.
14. SHEET A4.2; DETAIL 2: IS THE VERTICAL MEMBER A BRACE? VERIFY.
15. SHEET A6.0; DETAIL 7: IS THE VERTICAL MEMBER A BRACE? VERIFY. INDICATE HOW THE BRACING IS CONNECTED TO THE TOP OF THE PARTITION WALL.
16. SHEET A6.0; DETAIL 9: AT THE NOTE REFERENCE FOR THE BRACING TO THE ROOF, INDICATE THE SPECIFIC DETAIL.
17. GENERAL: PROVIDE A DETAIL TO INDICATE HOW THE BRACING IS CONNECTED TO THE STRUCTURE ABOVE.
18. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/18/2012 TERRY STEVENS ZONING REVIEW Approved
05/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the installed weight of the revised fan coil units. Provide structural calculations to verify that the existing roof is capable of supporting the fan coil units in close proximity and show the method of connecting the units to the building structure. Reference: Section 302.1, IMC 2006.
2. Revise the mechanical drawings to show the duct smoke detectors located upstream of any filters or outside air connections (the electrical power drawing shows duct smoke detectors located within the fan coils and note #4 on sheet M9.1 is incorrect). Reference: Section 606.2.1, IMC 2006.
3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
05/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/29/2012 ROBERT SHERRY WATER REVIEW Approved
05/29/2012 RSHERRY1 WWM REVIEW Passed No change to wastewater system.
06/05/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved