Permit Number: T12CM02529
Parcel: 105110710

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM02529
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/18/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Limiting the water velocity in Type L copper tubing to less than 8 FPS will result in maximum flow rates of 31 GPM, 44 GPM, and 77 GPM for 1-1/4", 1-1/2", and 2" size tubes. [Original comment: Revise the water pipe sizing table on sheet P0.0 for the pipes larger than 1" to limit the water velocity to less than 8 FPS for the copper piping. Reference: Table 604.4, footnote (c), IPC 2006, as amended by the City of Tucson.]
2. The World Market In-Store Sampling Guidelines call for the 3-compatment sink to be used to sanitize serving dishes with the wash-rinse-sanitize method. Per Section 802.1, IPC 2006, the wash and rinse compartments shall be directly-connected and the sanitize compartment shall be indirectly-connected to the sanitary drain system. [Original comment: Clarify the purpose of the 3-compartment sink in the break room; is it used solely for food preparation or will it also be used to clean serving items (e.g. the coffee airpots that are used daily in the store)? Reference: Section 802.1, IPC 2006.]