Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM02462
Parcel: 103200460

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM02462
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2012 SEPTIC APPROVAL WWM REVIEW Approved NO CHANGE IN F.U. EXISTING SEPTIC
05/24/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM02462
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FOUNDATION PLANS:

1. Show or notate a 6" minimum separation of untreated exterior posts above finished grade and metal pedestal base with 1" space above concrete, R319.1.4 exception 1.
2. Show compliance with termite treatment, R320.

STRUCTURAL PLANS:

1. Provide an engineer's calculation, design and seal for the bearing framed wall over 10' high without a compliant braced panel layout, R602.10.6.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R319.1 item 5. Clarify Detail 4/3.

PLUMBING PLANS:

1. Provide a gas line isometric showing pipe lengths and the BTU demand of each appliance. The supply pipe may require upgrading with the new developed length increase. G2413.3 & Table G2413.4(1).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2012 CINDY AGUILAR OUT TO CUSTOMER Completed