Permit Number - T12CM02450
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The revision to keynote #5 is now a compilation of Section 707.5, UPC 2006 and 708.3.3, IPC 2006. This plan was designed under the 2006 UPC; an additional cleanout is required for "each aggregate horizontal change of direction exceeding one-hundred and thirty-five (135) degrees". Do not conflate the two plumbing codes, the 100 feet mentioned in item #5 is strictly in the 2006 IPC. [Third comment: Comment not addressed.] [Second comment: The cover sheet for this plan set indicates that the 2006 Uniform Plumbing Code (UPC) has been used as the basis for design. Note #5 is appropriate for the 2006 International Plumbing Code (IPC) but is incorrect under the UPC. This has a direct impact on the required cleanouts for the restroom. As currently drawn, the restroom cleanouts are acceptable per Section 708.3.3, IPC 2006 but additional cleanouts will be required per Section 707.5, UPC 2006 (alternatively, the 4" drain could be straightened out to eliminate the problem). Changing the controlling code may result in additional comments.] [Original comment: See sheet P0.0- General Plumbing Notes: Sanitary and Vent Systems #5 is in reference to 2006 IPC 708.3.3. This plan is being reviewed per the 2006 UPC.] 2. The submitted drawing sets are incomplete and cannot be approved under any circumstances. Provide two complete sets of plans for approval. Any drawings that were previously approved should be included in the sets being submitted for approval otherwise additional time and review fees may be applicable. |
| 10/16/2013 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: McDonald's - 2525 S. Craycroft Road T12CM02450 Building Plan (4th Review) TRANSMITTAL DATE: October 16, 2013 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until a complete set of drawings is provided Zoning cannot approve the building plans. Provide a complete drawing set with your next submittal. 3. Sheet A1.0 the north arrow reference is not correct. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 12/04/2013 | CPIERCE1 | REJECT SHELF | Completed |