Permit Number: T12CM02408
Parcel: 123152790

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T12CM02408
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2012 MICHAEL ST. PAUL ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T12CM02408
1124 East Elm Street
New Second Unit


TRANSMITTAL: May 2, 2012


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO).


A DDO is required for the second unit in the rear yard for both the side-yard setbacks. This site is in the R-2 Zone (LUC Section 2.3.5.2.A.2). The Development Designator is "K" (LUC Section 3.2.3.1.C) and the Perimeter Yard Indicator BB (LUC Section 3.2.6.4).

The minimum setback for the east and west property lines is the greater of ten (10) feet or three-fourths (3/4) the height of the structure's wall facing each property line (LUC Sections 3.2.3.1.C & 3.2.6.4). The wall heights for the second unit are ten (10) feet on all sides. The minimum setback to each side yard is ten (10) feet (LUC Section 3.2.6.4). The proposed setback to the east property line is seven (7) feet, six (6) inches, and six (6) feet to the west property line.
05/02/2012 MICHAEL ST. PAUL NPPO REVIEW Passed
05/14/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Needs Review
05/14/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Needs Review