Permit Number: T12CM02356
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM02356
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A200; PARTITION TYPES: PER THE 2006 IBC SECTION 1607.13, INTERIOR PARTITIONS MUST BE ABLE TO RESIST A HORIZONTAL LOAD OF 5 PSF. ADD BRACING TO THE TOP OF THE PARTITION WALLS, INDICATING BRACING SIZE, SPACING, CONNECTION TO THE TOP OF THE PARTITION WALL, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE.
2. Minimum letter size both upper and lower case is 3/32", actual size. Sheets ASP1, A103 and M100 do not meet this standard. Please revise and resubmit.
END OF REVIEW
05/22/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the listing information for the specified thermostatic mixing valve. Reference: Sections 303.4 and 613.1, IPC 2006.
2. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 802.1 and 802.2, IPC 2006.
3. Clarify the reason for using an indirect waste connection for the bar and hand sinks (tags 8 and 14). Reference: Section 801.2, IPC 2006.
05/23/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
06/01/2012 GERRY KOZIOL WWM REVIEW Approved