Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM02356
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A200; PARTITION TYPES: PER THE 2006 IBC SECTION 1607.13, INTERIOR PARTITIONS MUST BE ABLE TO RESIST A HORIZONTAL LOAD OF 5 PSF. ADD BRACING TO THE TOP OF THE PARTITION WALLS, INDICATING BRACING SIZE, SPACING, CONNECTION TO THE TOP OF THE PARTITION WALL, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE. 2. Minimum letter size both upper and lower case is 3/32", actual size. Sheets ASP1, A103 and M100 do not meet this standard. Please revise and resubmit. END OF REVIEW |
| 05/22/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the listing information for the specified thermostatic mixing valve. Reference: Sections 303.4 and 613.1, IPC 2006. 2. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 802.1 and 802.2, IPC 2006. 3. Clarify the reason for using an indirect waste connection for the bar and hand sinks (tags 8 and 14). Reference: Section 801.2, IPC 2006. |
| 05/23/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/01/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |