Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM02356
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/01/2012 | FRODRIG2 | ZONING | REVIEW | Needs Review | |
05/01/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/01/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/01/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/01/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A200; PARTITION TYPES: PER THE 2006 IBC SECTION 1607.13, INTERIOR PARTITIONS MUST BE ABLE TO RESIST A HORIZONTAL LOAD OF 5 PSF. ADD BRACING TO THE TOP OF THE PARTITION WALLS, INDICATING BRACING SIZE, SPACING, CONNECTION TO THE TOP OF THE PARTITION WALL, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE. |
05/01/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
05/01/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
05/01/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
05/01/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
05/01/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
05/01/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |