Permit Number: T12CM02355
Parcel: 141153530

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM02355
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2012 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied Plan sheet E6.1
Please revise one line diagram . Voltage for existing ses in confict with dist. board "LDPA".
Please justify total loads as shown on load summary. Total new load 1952.4 amps is to close to service ratiing of 2000 amps.

For questions about this plan review contact Dan Santa-Cruz at 520-909-5173 or Dan.Santa Cruz@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/28/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed