Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM02355
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2012 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Plan sheet E6.1 Please revise one line diagram . Voltage for existing ses in confict with dist. board "LDPA". Please justify total loads as shown on load summary. Total new load 1952.4 amps is to close to service ratiing of 2000 amps. For questions about this plan review contact Dan Santa-Cruz at 520-909-5173 or Dan.Santa Cruz@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/28/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |