Permit Number: T12CM02349
Parcel: 105110710

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM02349
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/20/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/28/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T12CM02349
4380 N Oracle #100

1. Sheet E-2 shows the existing service entrance conductors to be used, they size at 4-600 mcm CU conductors rated at 420 amps per NEC 2005 310.16. The plan shows an 800 amp Service with a connected load of 166.3 amps and a future load of 531.5 amps ? Upgrade conductors to 800 amp capacity if to provide for a future load.
2. This Jurisdiction requires the grounding system of a service being upgraded to have a new grounding system installed, the existing one can be added to the new one.

Ray T Majuta
PDSD, C of Tucson
Electrical Plan Review,
6/28/2012