Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/20/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/20/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/28/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T12CM02349 4380 N Oracle #100 1. Sheet E-2 shows the existing service entrance conductors to be used, they size at 4-600 mcm CU conductors rated at 420 amps per NEC 2005 310.16. The plan shows an 800 amp Service with a connected load of 166.3 amps and a future load of 531.5 amps ? Upgrade conductors to 800 amp capacity if to provide for a future load. 2. This Jurisdiction requires the grounding system of a service being upgraded to have a new grounding system installed, the existing one can be added to the new one. Ray T Majuta PDSD, C of Tucson Electrical Plan Review, 6/28/2012 Ray.Majuta@tucsonaz.gov |