Permit Number: T12CM02349
Parcel: 105110710

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM02349
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2012 RONALD BROWN ADA REVIEW Passed
05/07/2012 MARTIN BROWN FIRE REVIEW Approved
05/09/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/11/2012 ROBERT SHERRY WATER REVIEW Approved
05/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy in the south space.
2. Clarify the water pipe sizing for the North space. The water calculations result in a 12.0 PSI per 100 ft. friction allowance, there is a statement that the pipe will be sized using a 5.0 PSI per 100 ft. friction allowance, and the pipe size chart is based on a 10.0 PSI per 100 ft. friction allowance. In all cases, the 1-1/2" water service pipe is undersized for the existing fixtures. Reference: Sections 106.3.1 and 604.1, IPC 2006.
05/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how access will be provided for the mechanical equipment serving the south space. Reference: Section 306.5, IMC 2006.
05/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM02349
4380 N Oracle, #100

1. Provide the size of conductors and conduits to be used from new SES to utility transformer.
2.The new SES will require a new grounding system, the
existing may be tied to SES, however new will be required.
3. Verify and notate on plan that existing equipment (MDP,L,T,DP,A,B,TL) rated for fault current as fault current
shcedules shows.
4. Sheet E-1 shows the transformer is located under panels MDP and DP ?
5. The existing feed to MDP is parallel sets of 600kcmil condutores rated at 840 amps, the fuse size is 400 amps ?
6. Indicate if new fixtures are Full Cutt Off.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
5/17/2012
Ray.Majuta@tucsonaz.gov
05/30/2012 GERRY KOZIOL WWM REVIEW Approved